arXiv · 2611.11229
GFM Control Automatic Compliance Toolbox
Abstract
The increasing penetration of converter-interfaced generation reduces system inertia, short-circuit strength, and voltage support. European grid codes, including the ENTSO-E Network Code on Requirements for Generators and the ACER Demand Connection Code, now define disturbance-based validation procedures for grid-forming (GFM) generation and converter-based demand. Commercial RMS tools, however, lack an integrated workflow aligned with these recent requirements. This paper presents an automated Python-PowerFactory compliance toolbox and an RMS test bench for a co-located system comprising a 1 MW GFM photovoltaic (PV) plant, a 0.3 MW GFM battery energy storage system (BESS), and a 1 MW converter-interfaced dynamic load at a 20 kV point of common coupling fed from a 110 kV grid. Extended virtual synchronous machine models and a DCC-oriented load model are tested in batch, with results automatically extracted and plotted for assessment. Results show compliant RMS performance for the slower, electromechanical tests, while the paper identifies which tests require complementary electromagnetic transient (EMT) verification.
Explore related subjects
Keep this discovery
Explore connections, maps & timelines
Tejas Kunbi, Rahul Rane, Dan Wu, Aleksandra Lekić. 2026-11-08. GFM Control Automatic Compliance Toolbox. https://arxiv.science/abs/2611.11229
Citations retain the original authors and DOI and include this site’s record URL. If this discovery service contributed to your research, you can also cite arXiv Science by Indiciae: BibTeX · RIS.