arXiv ScienceSearch

arXiv subjects

Shutang You

Publications and source records attributed to Shutang You.

At least 19 recordsLinked to original sources

Practical Power System Inertia Monitoring Based on Pumped Storage Hydropower Operation Signature

This paper proposes a practical method to monitor power system inertia using Pumped Storage Hydropower (PSH) switching-off events. This approach offers real-time system-level inertia estimation with minimal expenses, no disruption, and the inclusion of behind-the-meter inertia. First, accurate inertia estimation is achieved through improved RoCoF calculation that accounts for pre-event RoCoF, reducing common random frequency fluctuations in practice. Second, PSH field data is analyzed, highlighting the benefits of using switching-off events for grid inertia estimation. Third, an event detection trigger is designed to capture pump switching-off events based on local and system features. Fourth, the method is validated on the U.S. Eastern Interconnection model with over 60,000 buses, demonstrating very high accuracy (3%-5% error rate). Finally, it is applied to the U.S. Western Interconnection, with field validation showing a 9.9% average absolute error rate. Despite challenges in practical power system inertia estimation, this method enhances decision-making for power grid reliability and efficiency, addressing challenges posed by renewable energy integration.

eess.SY

Build Smart Grids on Artificial Intelligence -- A Real-world Example

Power grid data are going big with the deployment of various sensors. The big data in power grids creates huge opportunities for applying artificial intelligence technologies to improve resilience and reliability. This paper introduces multiple real-world applications based on artificial intelligence to improve power grid situational awareness and resilience. These applications include event identification, inertia estimation, event location and magnitude estimation, data authentication, control, and stability assessment. These applications are operating on a real-world system called FNET-GridEye, which is a wide-area measurement network and arguably the world-largest cyber-physical system that collects power grid big data. These applications showed much better performance compared with conventional approaches and accomplished new tasks that are impossible to realized using conventional technologies. These encouraging results demonstrate that combining power grid big data and artificial intelligence can uncover and capture the non-linear correlation between power grid data and its stabilities indices and will potentially enable many advanced applications that can significantly improve power grid resilience.

eess.SY

Adaptive Frequency-Regulation Demand Response Using Substation Solar Irradiance Measurement in High-PV Power Systems

This letter proposes a distributed and adaptive demand response approach for primary frequency regulation in high-PV power systems. Using solar irradiance measurement at substations, the proposed approach allows accurate estimation of real-time system inertia of high-PV systems, thus facilitating the estimation of power imbalance after a contingency. The test results from the U.S. Electric Reliability Council of Texas (ERCOT) high-PV penetration models validated its effectiveness.

eess.SY

Large-Scale High PV Power Grid Dynamic Model Development -- A Case Study on the U.S. Eastern Interconnection

Power systems are undergoing a transformation toward a low-carbon non-synchronous generation portfolio. A major concern for system planners and operators is the system dynamics in the high renewable penetration future. Because of the scale of the system and numerous components involved, it is extremely difficult to develop high PV dynamic models based upon actual power system models. The main contribution of this paper is providing an example of developing high PV penetration models based on the validated dynamic model of an actual large-scale power grid - the U.S. Eastern Interconnection system. The displacement of conventional generators by PV is realized by optimization. Combining the PV distribution optimization and the validated dynamic model information, this approach avoids the uncertainties brought about by transmission planning. As the existing dynamic models can be validated by measurements, this approach improves the credibility of the high PV models in representing future power grids. This generic approach can be applied to develop high PV dynamic models for other actual large-scale systems.

eess.SY

Compressive Sensing Based Situational Awareness and Sensor Placement for DC Microgrids with Relatively Fixed Operation Patterns

This paper proposes a DC microgrid state estimation and sensor placement method based on compressive sensing. Formulations of various types of measurements and components are developed under the proposed framework. A measurement placing strategy to minimize the coherence of the measurement matrix and thus increase estimation accuracy is presented. Simulation results show that the proposed state estimation and sensor placing approach can effectively reduce the number of sensors to achieve a certain level of estimation accuracy.

eess.SY

Photovoltaic (PV) Virtual Inertia and Fast Frequency Regulation in High PV Power Grids

This paper studies the frequency response using PV. Multiple control strategies are considered and simulated in the high PV ERCOT model, including inertia control, synthetic governor control, and AGC control. The impact of different parameters in PV inertia control and their correlation and impact on frequency response are analyzed. The simulation results show that PV farm has potential to provide multiple types of grid service to support system frequency. This paper also proposed a distributed fast frequency control approach that can better leverage the PV headroom reserve to improve the system frequency nadir after contingencies.

eess.SY

A Simulation-based Education Approach for the Electromagnetic and Electromechanical Transient Waves in Power Systems

Power systems usually go through electromagnetic and electromechanical transient processes after different disturbances. Learning the characteristics and the differences between them are important but not easy for students majoring in power systems. This paper presents a simulation-based approach to comprehensively study the two types of transient waves, constituting the experimental part of the power system transient and stability course. In this approach, three models with different levels of complexity are developed to simultaneously show the two types of transient waves in the time domain. The developed models are then demonstrated as testbeds for investigating various aspects related to the two types of transient, such as waveforms induced by different disturbances, influencing factors on the propagation speed, and the interaction between incident waves and the reflective waves. In addition, a theory-to-practice engineering research process is demonstrated through developing a power system event-location application, which is inspired by electromechanical wave propagation study. The proposed education process and models at various complexity levels provide a creative and interactive way for power system transients and dynamics study.

eess.SY

Frequency Response Study on the ERCOT under High Photovoltaic (PV) Penetration Conditions

Solar photovoltaic (PV) generation is growing rapidly around the world. However, PV generation, based on inverter, is fundamentally different from conventional synchronous generators. It is of vital importance to understand the impacts of increased penetration of PV generation on power system dynamic performance. This paper investigates frequency response of the Electric Reliability Council of Texas (ERCOT) with high PV penetration in the future year. In this work, a realistic baseline dynamic model is validated using synchrophasor measurements. Then, dynamic simulation is performed to evaluate the impacts of high PV generation on frequency response.

eess.SY

Calculate Center-of-Inertia Frequency and System RoCoF Using PMU Data

The power system frequency is important for the system overall stability. However, there does not exist a single measurement point of the system frequency due to the distributed nature of the system inertia and the small inconsistency of different generator rotor electrical speeds in one synchronized system. This paper proposed a new approach to calculate the system center-of-inertia (COI) frequency and the rate-of-change-of-frequency (RoCoF) more accurately using PMU data at multiple locations. The COI frequency and the RoCoF value were further used to assist fast estimation of the imbalance MW amount of a frequency event. Test results using actual measurements in the U.S. Eastern Interconnection system validated the effectiveness of the proposed method.

eess.SY

Solar PV Frequency Control in the U.S. EI and ERCOT Interconnections -- Case Studies and Recommendations

This paper studied the solar PV frequency control in the U.S. Eastern Interconnection (EI) and Texas Interconnection (ERCOT) systems. The studied frequency control approaches include droop frequency control, inertia control, and droop-inertia-combined frequency control. The control effects of different frequency controls of PV in the EI and ERCOT are studied using actual high PV penetration interconnection grid models to provide suggestions to the future revision of future PV frequency control standards.

eess.SY

Frequency Response Characteristic (FRC) Curve and Fast Frequency Response Assessment in High Renewable Power Systems

This paper introduces a frequency response characteristic (FRC) curve and its application in high renewable power systems. In addition, the paper presents a method for fast frequency response assessment and frequency nadir prediction without performing dynamic simulations using detailed models. The proposed FRC curve and fast frequency response assessment method are useful for operators to understand frequency response performance of high renewable systems in real time.

eess.SY

Wind Power Transmission System Integration -- a Case Study of China Wind Power Base

Due to a series of supporting policies in recent years, China wind power has developed rapidly through a large-scale and centralized mode. This paper analyzes the two major concerns faced by wind power development in China: wind generation reliability and wind energy balancing. More specifically, wind farm tripping-off-grid incidents and wind power curtailment issues, which caused huge economical loss, are investigated in details. Based on operation experience of large wind power bases, technical recommendations and economic incentives are proposed to improve wind power integration and power grid reliability. As a summary and outlook of wind power development in China, this paper provides a reference on future wind power development for other countries.

eess.SY

Large-scale Interconnection Power System Model Sanity Check, Tuning, and Validation for Frequency Response Study

The quality and accuracy of power system models is critical for simulation-based studies, especially for studying actual stability issues in large-scale systems. With the deployment of wide-area monitoring systems (WAMSs), the high-reporting-rate frequency measurement provides a trustworthy ground truth for validating models in frequency response studies. This paper documented an effort to check, tune, and validate the U.S. power system model based on a WAMS called FNET/GridEye. Four metrics are used to quantitatively compare the simulation results and the actual measurement, including frequency nadir, RoCoF, settling frequency and settling time. After tuning governor deadband and the governor ratio, the model frequency response shows significant improvement and matches well with the event measurement data. This work serves as an example for tuning and validating large-scale power system models.

eess.SY

Impact of High PV Penetration on Regional Power Grids

Due to the high solar irradiance or energy price, certain regions in the U.S. may reach 100% PV penetration and experience degradation of frequency response greater than the interconnection as a whole. Therefore, in this section, the 100% PV penetration region in each interconnection is simulated to study the local high PV penetration effects. The study was performed by quantifying RoCoF, frequency nadir, and settling frequency at different regional PV penetration levels. The impact of high regional PV penetration on the compliance of grid code on frequency response is also studied.

physics.soc-ph

Locate the Source of Resonance-Involved Forced Oscillation in Power Systems Based on Mode Shape Analysis

This paper proposed a new method to locate the source of forced oscillation that involves resonance with natural oscillation modes. The new method is based on comparing the oscillation mode shape of the forced oscillation with that of the natural oscillation that the forced oscillation resonating with. The location that has the largest angle difference between the forced oscillation mode and the natural oscillation mode usually indicates the location of the driving force in forced oscillations. Some examples in actual U.S. EI system verified this approach.

eess.SY

A Quantum Computing Framework for Complex System Reliability Assessment

This paper proposed a framework based on quantum computing for reliability assessment of complex systems. The 'Quantum Twin' concept was also proposed. The framework can be used to accelerate the reliability assessment of large-scale complex systems, which could take much computation time for classical computers to achieve accurate results. Power system is used as an example of complex systems to illustrate the framework.

eess.SY

Determine Disturbance Locations in Power Grids using Bicubic 2D Interpolation on Electromechanical Wave-front Propagation Delay

This study presents a method to locate power system disturbance using wide-area synchrophasor measurements. The merits of the proposed method include robustness and easy for visualization. In addition, the proposed method facilitates the calculation of electromechanical wave propagation speed distribution. An example of locating the disturbance and generating the propagation speed distribution is demonstrated based on FNET/GridEye, a distribution-level wide-area measurement system. Without losing generality, the proposed method can be implemented in any other wide-area measurement systems.

eess.SY

Impact of High Penetration of Inverter-based Generation on Electromechanical Wave Propagation in Power Grids

A power system electromechanical wave propagates from the disturbance location to the rest of system, influencing various types of protections. In addition, since more power-electronics-interfaced generation and energy storage devices are being integrated into power systems, electromechanical wave propagation speeds in the future power systems are likely to change accordingly. In this paper, GPS-synchronized measurement data from a wide-area synchrophasor measurement system FNET/GridEye are used to analyze the characteristics of electromechanical wave propagation in the U.S. Eastern Interconnection (EI) system. Afterwards, high levels of photovoltaic (PV) penetration are modeled in the EI to investigate the influences of a typical power-electronics--interfaced resource on the electromechanical wave propagation speed. The result shows a direct correlation between the local penetration level of inverter-based generation and the electromechanical wave propagation speed.

eess.SY