arXiv · 2611.23504
Profile Screening and Frequency-Secure Operating Limit Derivation for Data Center Microgrids
Abstract
Rapid power variations from artificial intelligence (AI) workloads pose frequency-security challenges for islanded data-center microgrids. This paper proposes a generator step- response-based framework to rapidly screen candidate load pro- files and derive frequency-secure operating limits for IT workload scheduling. Identified generator responses are superimposed to assess the cumulative frequency effects of successive load changes without repeated dynamic simulations. The framework identifies potentially unsafe intervals and determines allowable load magni- tudes, ramp rates, and minimum event spacing, while accounting for prediction uncertainty and governor limits. Validation on a 2.5 MVA islanded microgrid with eight generator configurations and 14 synthetic AI workload profiles shows that 94.75% of 40,208 assessment windows receive decisive screening labels, with no frequency-violating windows classified as secure.
Explore related subjects
Keep this discovery
Explore connections, maps & timelines
Zishuo Yang, Yu Ma, Jong Ha Woo, Aaditya Pandey, Wenyuan Tang, Chau-Wai Wong, Ning Lu. 2026-11-17. Profile Screening and Frequency-Secure Operating Limit Derivation for Data Center Microgrids. https://arxiv.science/abs/2611.23504
Citations retain the original authors and DOI and include this site’s record URL. If this discovery service contributed to your research, you can also cite arXiv Science by Indiciae: BibTeX · RIS.