arXiv · 2611.19132
The Race between Protection and Control: Fast Reactive Reserves Against Overvoltage Cascade
Abstract
In an overvoltage cascade, each relay trip removes reactive power absorption and raises the voltage at other plants, often faster than controls can act. This paper determines how much fast reactive power to hold, where, and how fast, so that no contingency trips a plant. A trip certificate allows a relay to pick up if it resets before its delay expires, making the sizing a linear program. A necessary condition identifies the relays that only preventive action can protect, and the reserve of one control decreases with the relay delay and increases with its latency. In nonlinear simulations of four systems, the corrective actions prevent every trip within the analysis window for relays without reset hysteresis, and each plant's own set point is the most effective reserve. A 2\% hysteresis or a small error in the relay voltage can change the reserve as much as the relay delay.
Explore related subjects
Keep this discovery
Explore connections, maps & timelines
Abdallah Alalem Albustami, Mads Almassalkhi, Ahmad F. Taha. 2026-11-14. The Race between Protection and Control: Fast Reactive Reserves Against Overvoltage Cascade. https://arxiv.science/abs/2611.19132
Citations retain the original authors and DOI and include this site’s record URL. If this discovery service contributed to your research, you can also cite arXiv Science by Indiciae: BibTeX · RIS.