Hyperscale Data Centers as Wide-Area Damping Actuators for Low-Inertia Power Systems
Abstract
Low-inertia power systems need fast damping actuators as synchronous generation is displaced by inverter-based resources. This paper evaluates hyperscale data-center loads controlled through Dynamic Voltage and Frequency Scaling (DVFS) as wide-area damping actuators. A DAE-consistent bus-input matrix is validated against the ANDES reduced state matrix and a finite-difference input check. On the Kundur two-area benchmark, Bus 10 ranks highest among non-generator buses for the 0.647 Hz inter-area mode. A classical washout-plus-lead-lag controller raises damping from 3.43% to approximately 6%. Modern 10-50 ms battery and DVFS actuators require comparable peak modulation for the same small-signal damping target. Compared with a closest same-system data-center-frequency-droop baseline, the wide-area controller offers a clearer advantage: at comparable peak MW, droop reaches 4.76% damping, while reaching 6% requires approximately twice the peak modulation. In the Pade-delay model, damping crosses the open-loop value at 443 ms for the 10 ms DVFS actuator versus 374 ms for the 50 ms BESS case. Reduced-order saturation stress tests show that a 2 MW envelope is non-binding for modal, fault-cleared-equivalent, and line-outage-equivalent disturbances, but can bind under generator-trip-equivalent stress. IEEE 39-bus tests confirm the DAE-based ranking procedure and show that high-residue buses may require more phase compensation than a single lead-lag stage can supply.
Explore related subjects
Keep this discovery
Explore connections, maps & timelines
Mohamed Shamseldein. 2026-10-24. Hyperscale Data Centers as Wide-Area Damping Actuators for Low-Inertia Power Systems. https://doi.org/10.1007/s40866-026-00358-5
Cite the original work for its findings. Save a collection to share your selection of sources.