Convex Inner Approximations for Safe AC Dispatch With Device Dynamics

Abstract

Safe AC dispatch requires both feasible operating points and enough ramping capability to reach the next target. This paper constructs convex inner approximations that connect nonlinear network feasibility, constrained device response, and dispatch-interval tracking. A fixed-point certificate enforces AC operating limits under bounded load uncertainty. Componentwise response envelopes convert heterogeneous device dynamics into affine conditions on measured states and power references. A command governor then combines these conditions with available ramping capability and a hard terminal-error bound. It selects an admissible target through a minimum-deviation objective and holds the corresponding reference while reserved fast regulation remains active. The resulting quadratic program has no network-trajectory decision variables. Tests on the IEEE 39- and 118-bus systems include 96 single-target executions and 64 transitions in continuous dispatch sequences at five- and fifteen-minute intervals. All 160 transitions satisfy the AC constraints, independent balancing-generator capability checks, and the prescribed regulation-adjusted terminal accuracy. A paired ablation verifies the contribution of the terminal condition under slow device responses. Complete admission-cycle computation has median times of 3.45 and 8.79 ms for the two systems. The construction provides a tractable link between available ramping capability and safe, timely execution of AC dispatch.

Explore related subjects

Keep this discovery

Explore connections, maps & timelines

BibTeXRIS

Ziqing Zhu. 2026-10-19. Convex Inner Approximations for Safe AC Dispatch With Device Dynamics. https://arxiv.org/abs/2610.26634

Cite the original work for its findings. Save a collection to share your selection of sources.

KEEP EXPLORING

Related papers

Braess' Paradoxes in Coupled Power and Transportation Systems

Transportation electrification introduces strong coupling between the power and transportation systems. In this paper, we generalize the classical notion of Braess' paradox to coupled power and transportation systems, and examine how the cross-system coupling induces new types of Braess' paradoxes. To this end, we model the power and transportation networks as graphs, coupled with charging points connecting to nodes in both graphs. The power system operation is characterized by the economic dispatch optimization, while the transportation system user equilibrium models travelers' route and charging choices. By analyzing simple coupled systems, we demonstrate that capacity expansion in either the transportation or the power system can deteriorate the performance of both systems, and uncover the fundamental mechanisms for such new Braess' paradoxes to occur. We also provide necessary and sufficient conditions for the occurrence of Braess' paradoxes in general coupled systems, leading to managerial insights for infrastructure planners. For general networks, by characterizing generalized user equilibria of coupled systems, we develop charging-pricing policies to mitigate Braess' paradoxes.

eess.SY↗

Analytical Prediction of Voltage Collapse in Current-Limited Grid-Forming Inverters

As converter-interfaced units become dominant in power systems, understanding nonlinear stability phenomena involving discrete switching events becomes essential for secure operation. The limited overcurrent capability of grid-forming (GFM) inverters makes current limiting essential during large disturbances. Activation of a circular current limiter (CCL) can cause the operating equilibrium to disappear under certain circumstances. This paper develops an analytical framework to predict the grid-voltage boundaries for CCL activation and determine whether the operating equilibrium persists or disappears after activation. For CCL-based GFM inverters with frozen anti-windup, closed-form expressions for the activation boundaries are derived while accounting for the filter capacitor. A criterion is established to determine whether a saturated (i.e., current-limited) stable equilibrium point (satSEP) persists following limiter activation. A continuation method is also developed to trace equilibria across normal-control and current-limited operation. Power-angle analysis and dynamic-model continuation in single-inverter and modified 9-bus systems validate these predictions. Time-domain simulations further confirm the results. The results show that CCL activation can either cause immediate loss of the stable equilibrium or allow stable current-limited operation to continue until the equilibrium is lost as operating conditions change further.

eess.SY↗

Reduced Arc-Weight Heterogeneity for Master Stability Analysis of Directed Networks

Master stability analysis can be applied to directed networks even when their Laplacian matrices are not diagonalizable. Nevertheless, a diagonalizable Laplacian is easier to analyse because the perturbations governing synchronization separate into independent modes. This paper asks how many different positive coupling strengths are needed to obtain this simplification without adding or removing any directed connections. We first give an elementary construction showing that suitable positive weights exist for every weakly connected directed network and explain its relationship to stronger genericity results in the literature. We then introduce a measure of the smallest number of distinct coupling strengths required for diagonalizability. If a common coupling strength already produces a diagonalizable Laplacian, only one value is needed. For directed acyclic networks, we give a constructive upper bound based on the length of the longest directed path from a source. This bound is exact for rooted outward directed trees. Consequently, an outward star requires only one coupling value, whereas a directed path requires a different value on every arc. These results reduce coupling heterogeneity while retaining the simpler modal form of master stability analysis. Diagonalizability is treated as an analytical convenience, not as a sufficient condition for synchronization.

eess.SY↗