Fast Reassessment of Prolonged Electricity Shortages under Shared Fuel Interruptions

Abstract

When several generators share a fuel supply, one interruption can disable them together and cause electricity shortages lasting days. Such interruptions can be made less frequent, for example by weatherizing gas supply, or shorter, for example by on-site backup fuel. Yet traditional resource adequacy indices, expected unserved energy and loss-of-load hours, fail to distinguish such measures whenever they remove the same expected time without fuel, because for interruptions independent of system conditions these indices depend on the interruptions only through this time. Their difference is revealed by prolonged-shortage exposure, the expected annual hours in shortages of at least a given duration, whose exact chronological calculation must be repeated for every interruption scenario. To reduce this cost, a fast reassessment method with guaranteed accuracy is proposed. Network calculations are performed once and condensed into a restoration response, the additional prolonged-shortage hours caused by one interruption of each duration, from which any scenario is evaluated as a weighted sum without new simulation. An hour-by-hour error bound determines whether this evaluation is accurate enough, and exact dynamic programming is applied otherwise, so that every result lies within a requested tolerance of the exact value on the same Monte Carlo samples. On the Reliability Test System of the Grid Modernization Laboratory Consortium, most evaluations were accepted, fully accepted scenarios typically ran more than 200 times faster than exact calculation, and total computation time decreased in every workload. Measures against fuel interruptions can thus be screened quickly and accurately by their effect on prolonged shortages.

Explore related subjects

Keep this discovery

Explore connections, maps & timelines

BibTeXRIS

Dogan Urgun. 2026-10-19. Fast Reassessment of Prolonged Electricity Shortages under Shared Fuel Interruptions. https://arxiv.org/abs/2610.26265

Cite the original work for its findings. Save a collection to share your selection of sources.

KEEP EXPLORING

Related papers

Braess' Paradoxes in Coupled Power and Transportation Systems

Transportation electrification introduces strong coupling between the power and transportation systems. In this paper, we generalize the classical notion of Braess' paradox to coupled power and transportation systems, and examine how the cross-system coupling induces new types of Braess' paradoxes. To this end, we model the power and transportation networks as graphs, coupled with charging points connecting to nodes in both graphs. The power system operation is characterized by the economic dispatch optimization, while the transportation system user equilibrium models travelers' route and charging choices. By analyzing simple coupled systems, we demonstrate that capacity expansion in either the transportation or the power system can deteriorate the performance of both systems, and uncover the fundamental mechanisms for such new Braess' paradoxes to occur. We also provide necessary and sufficient conditions for the occurrence of Braess' paradoxes in general coupled systems, leading to managerial insights for infrastructure planners. For general networks, by characterizing generalized user equilibria of coupled systems, we develop charging-pricing policies to mitigate Braess' paradoxes.

eess.SY↗

Analytical Prediction of Voltage Collapse in Current-Limited Grid-Forming Inverters

As converter-interfaced units become dominant in power systems, understanding nonlinear stability phenomena involving discrete switching events becomes essential for secure operation. The limited overcurrent capability of grid-forming (GFM) inverters makes current limiting essential during large disturbances. Activation of a circular current limiter (CCL) can cause the operating equilibrium to disappear under certain circumstances. This paper develops an analytical framework to predict the grid-voltage boundaries for CCL activation and determine whether the operating equilibrium persists or disappears after activation. For CCL-based GFM inverters with frozen anti-windup, closed-form expressions for the activation boundaries are derived while accounting for the filter capacitor. A criterion is established to determine whether a saturated (i.e., current-limited) stable equilibrium point (satSEP) persists following limiter activation. A continuation method is also developed to trace equilibria across normal-control and current-limited operation. Power-angle analysis and dynamic-model continuation in single-inverter and modified 9-bus systems validate these predictions. Time-domain simulations further confirm the results. The results show that CCL activation can either cause immediate loss of the stable equilibrium or allow stable current-limited operation to continue until the equilibrium is lost as operating conditions change further.

eess.SY↗

Reduced Arc-Weight Heterogeneity for Master Stability Analysis of Directed Networks

Master stability analysis can be applied to directed networks even when their Laplacian matrices are not diagonalizable. Nevertheless, a diagonalizable Laplacian is easier to analyse because the perturbations governing synchronization separate into independent modes. This paper asks how many different positive coupling strengths are needed to obtain this simplification without adding or removing any directed connections. We first give an elementary construction showing that suitable positive weights exist for every weakly connected directed network and explain its relationship to stronger genericity results in the literature. We then introduce a measure of the smallest number of distinct coupling strengths required for diagonalizability. If a common coupling strength already produces a diagonalizable Laplacian, only one value is needed. For directed acyclic networks, we give a constructive upper bound based on the length of the longest directed path from a source. This bound is exact for rooted outward directed trees. Consequently, an outward star requires only one coupling value, whereas a directed path requires a different value on every arc. These results reduce coupling heterogeneity while retaining the simpler modal form of master stability analysis. Diagonalizability is treated as an analytical convenience, not as a sufficient condition for synchronization.

eess.SY↗