arXiv · 2610.17606
Constrained Grid-Forming Control for Photovoltaic Systems: A Control Barrier Function Approach
Abstract
This paper leverages control barrier functions (CBFs) to systematically account for constraints of voltage source converters (VSCs) and photovoltaic (PV) resources in grid-forming (GFM) control. The proposed control combines (unconstrained) dual-port GFM control with control barrier functions (CBFs) to ensure reliable and safe operation of a GFM PV system under grid faults, sudden changes in irradiance, and load perturbations. First, CBFs are used to encode physical and operational limits of the PV system, namely current and voltage limits at its ac and dc terminals. Then, CBFs are used to restrict the dynamics of dual-port GFM control to within the VSC and PV limits during both transient and steady states. To this end, a cost function is defined that encodes trade-offs between forming the ac voltage phase angle/frequency and voltage magnitude under constraints. Then, real-time optimization is used to make the least modification, as measured by the cost function, to the (unconstrained) dual-port GFM control state to remain within the safe set encoded by the CBFs. Finally, the performance of the developed constrained GFM control is evaluated through EMT simulations in MATLAB/Simulink.
Explore related subjects
Keep this discovery
Explore connections, maps & timelines
Amir Afshari, Dominic Groß. 2026-10-13. Constrained Grid-Forming Control for Photovoltaic Systems: A Control Barrier Function Approach. https://arxiv.org/abs/2610.17606
Cite the original work for its findings. Save a collection to share your selection of sources.