Electric Grid Topology and Admittance Estimation: Quantifying Phasor-based Measurement Requirements
Abstract
In this paper, we quantify voltage and current phasor-based measurement requirements for the unique estimation of the electric grid topology and admittance parameters. Our approach is underpinned by the concept of a rigidity matrix that has been extensively studied in graph rigidity theory. Specifically, we show that the rank of the rigidity matrix is the same as that of a voltage coefficient matrix in a corresponding electric power system. Accordingly, we show that there is a minimum number of measurements required to uniquely estimate the admittance matrix and corresponding grid topology. By means of a numerical example on the IEEE 4-node radial network, we demonstrate that our approach is suitable for applications in electric power grids.
Explore related subjects
Keep this discovery
Explore connections, maps & timelines
Norak Rin, Iman Shames, Ian R. Petersen, Elizabeth L. Ratnam. 2024-10-23. Electric Grid Topology and Admittance Estimation: Quantifying Phasor-based Measurement Requirements. https://arxiv.org/abs/2410.17553