arXiv · 1209.4299
Dynamic PID loop control
Abstract
The Horizontal Test Stand (HTS) SRF Cavity and Cryomodule 1 (CM1) of eight 9-cell, 1.3GHz SRF cavities are operating at Fermilab. For the cryogenic control system, how to hold liquid level constant in the cryostat by regulation of its Joule-Thompson JT-valve is very important after cryostat cool down to 2.0 K. The 72-cell cryostat liquid level response generally takes a long time delay after regulating its JT-valve; therefore, typical PID control loop should result in some cryostat parameter oscillations. This paper presents a type of PID parameter self-optimal and Time-Delay control method used to reduce cryogenic system parameters' oscillation.
Explore related subjects
Keep this discovery
L. Pei, A. Klebaner, J. Theilacker, W. Soyars, A. Martinez, R. Bossert, B. DeGraff, C. Darve. 2012-09-19. Dynamic PID loop control. https://arxiv.org/abs/1209.4299
Cite the original work for its findings. Save a collection to share your selection of sources.